Page 2 OSRAM - operating instructions: TOUCH DIM PD LI 2P WOS
Wiring diagram
Mounting hints
The sensor is connected to a 3 wire cable which is admitted for mains voltage. Parallel connection of
several sensors is not allowed. The sensor is typically installed in luminaires, ceiling installation is
possible by use of a flush device box and an adequate cover.
Following sensor heads are approved to be used with the Touch DIM PD LI 2P WOS sensor:
(-> sensor head not
included in delivery)
PANASONIC NaPiOn sensors (passiv infrared)
Digital version
- Standard type Standard anthracite AMN11111
(5m range) white AMN11112
Economy anthrazit AMN31111
white AMN31112
- Type for small movements Standard anthracite AMN12111
white AMN12112
Economy anthracite AMN32111
white AMN32112
- Spot type
Standard anthracite AMN13111
white AMN13112
Economy anthracite AMN33111
white AMN33112
- 10m type Standard anthracite AMN14111
white AMN14112
Economy anthracite AMN34111
white AMN34112
When adding a sensor head to the sensor, please note the following:
The entire workplace must lie within the monitoring cone of the sensor.
The sensor must not be exposed to drafts (e.g. near air vents). A draft could be misinterpreted as
the presence of a person in the room.
ECG QTi DALI
Lamp
1
2
3
4
DA
DA
~
~
ECG QTi DALI
Lamp
1
2
3
4
DA
DA
~
~
N
PE
Push button
(manual
control)
L
TOUCH DIM
Sensor
ECG QTi DALI
Lamp
1
2
3
4
DA
DA
~
~
ECG QTi DALI
Lamp
1
2
3
4
DA
DA
~
~
max. 4
QTi ECG
or HTi
transform
ers
L
N S
signal wire length max. 10m
Push button and sensor have to be
connected to the same mains phase!